This diagram shows a solution where one PLC is coupled to
two redundant control stations via the IEC 60870-5-104 protocol.
At the
Profibus, ipConvLite/MEC2PBS functions as a slave and the PLC as a master, the
DPV0 Profibus version is used.
In control direction, IEC 60870-5-104 switching commands or set points are mapped to the Profibus DPV0 input section.
In monitoring direction, digital and analog outputs are mapped to IEC 60870-5-104 information objects.
How data is allocated is freely configurable. Time stamps can be added in ipConvLite/MEC2PBS.
This diagram shows a solution where an PLC, which assumes the role of a control station, is connected to one or several substations. Two different serial protocols IEC 60870-5-101 and DNP 3.0 are used.
The digital and analog PLC outputs are mapped to commands in the RTU direction.
In the monitoring direction, the information objects from IEC 60870-5-101 and/or DNP 3.0 are mapped to digital and/or analog inputs.
A similar topography was used for the IBIRITE project.