SEC3

Compact controller for DIN rail mounting for small and distributed applications

  • SEC3 is an embedded controller designed for use in industrial applications. It has no rotating parts. A fan is not required due to the low power requirement.

    SEC3 has two serial RS232/RS422/RS485 interfaces and two Ethernet adapters. Thanks to a redundant power feed-in, different input voltages can be used.

    SEC3 is used in combination with the products ipRoute, ipConvLite and ip4Cloud. The system is supplied with the newest version of our real-time ipLinux operating system.

    The device is equipped with a status relay, which can be freely configured by the software. In the case of power failures or non-fulfillment of a user-defined condition a changeover switch switches into the idle state "FAIL".

    Various diagnostic functions are available via built-in LEDs. A power indicator, transmit and receive indicator for the serial interfaces as well as an indicator for the network controller provide information about the current operating status. A CPU LED indicates the operating mode of the software.

Performance Overview
  • Graphical comparison of IPCOMM gateways with regard to the maximum number of information changes/s at 100% throughput and the maximum number of node variables that can be managed, processed and transmitted.

    Gateway Performance Charts

Technical Details
  • Processor

    ARM Cortex-A8 1 GHz

  • Mass Storage

    512 MB SLC NAND Flash

  • Memory

    256 MB DDR3L

  • Network Interface

    2x RJ45 10/100BASE-T

  • Serial interfaces

    2x RJ45 RS232 / RS422 / RS485
    Baud Rate: 300 – 115200 Baud

  • USB interface

    2 x USB 2.0 up to 480 Mbps

  • State relay "FAIL"

    Maximum voltage: 30 V AC/DC
    Maximum current: 2 A

  • ESD

    All interfaces are ESD protected
    (ESD, surge and burst see EMC)

  • Diagnostics (Status LEDs)

    PWR: Power LED
    USR: LED freely configurable by software
    CPU: LED to show different software conditions
    COM1/COM2: Send and receive LED for serial interfaces
    ETH0/ETH1: Link and activity LED for Ethernet interfaces

  • Additional functions

    Battery bufferd real time clock (RTC)
    State relay "FAIL"
    Hardware watchdog
    Temperature monitoring
    Power supply monitoring

  • Power supply

    UPWR1/2: 12 / 24 / 48 V DC (9 – 60 V DC)

  • Power consumption

    Max. 10 W (typ. 4 W without USB)

  • Line cross-section

    0.13 – 3.31 mm² (AWG 26...12, solid or stranded wire)

  • Feature

    Redundant feed-in with fault contact "FAIL"

  • Dimensions W/H/D

    approx. 50mm/124mm/122mm

  • Mounting

    35 mm DIN-Rail

  • IP Code

    IP30

  • Rotating parts

    None

  • Weight

    approx. 0.4 kg

  • Environmental- / storage temperature

    -20° C to 60° C / -40° C to 85° C

  • Rel. humidity

    5 % to 95 % non-condensing

  • Approval

    CE (Industrial)
    UKCA

  • Standards

    EN 61000-6-2: 2005
    EN 61000-6-3: 2007+ A1:2011
    EN 61850-3: 2014 1) (only SEC3-SA)

  • Conformity

    RoHS
    REACH
    WEEE

  • Electromagnetic Compatibility (EMC) – Emission Requirements:

    EN 55016-2-1:2014
    Conducted emission on power supply lines in the frequency range 150 kHz - 30 MHz
    EN 55016-2-1:2014
    Conducted emission on telecommunication lines in the frequency range 150 kHz - 30 MHz
    EN 55016-2-3:2010 + A1:2010 + AC:2013 + A2:2014
    Radiated emission in the frequency range 30 MHz - 1 GHz
    EN 55016-2-3:2010 + A1:2010 + AC:2013 + A2:2014
    Radiated emission in the frequency range 1 GHz – 6 GHz

  • Electromagnetic Compatibility (EMC) – Immunity Requirements

    EN 61000-4-2: 2009
    Electrostatic discharge (ESD)
    - Contact discharge ± 6 kV
    - Air discharge ± 8 kV
    EN 61000-4-3: 2006 + A1:2008 + A2:2010
    Immunity to RF electromagnetic fields in the frequency range 80 – 3000 MHz, Test level 10 V/m
    EN 61000-4-4: 2012
    Immunity to fast transients (Burst)
    - DC power port ± 2 kV
    - Signal lines ± 2 kV
    EN 61000-4-5: 2014
    Immunity to surges on power supply lines (Surge)
    - DC power port: line <-> ground ± 2 kV
    - DC power port: line <-> line ± 1 kV
    EN 61000-4-5: 2014
    Immunity to surges on shielded signal lines (Surge)
    - Shielded lines ± 1 kV
    EN 61000-4-6: 2014
    Immunity to conducted interference induced by radio-frequency fields in the frequency range 150 kHz – 80 MHz, Test level 10 V
    EN 61000-4-12: 1995 + A1:2001
    Immunity to ring wave
    - Frequency 100 kHz / 1MHz
    - Power port DC ± 1.25 kV line to line
    - Data lines ± 2.5 kV line to ground
    EN 61000-4-16: 1998 + A:2004 + A2:2011
    Immunity to conducted interference induced by lowfrequency fields
    - Short (1s): 16⅔ Hz / 50 Hz / 60 Hz – 100 V
    - Continuous: 16⅔ Hz / 50 Hz / 60 Hz – 10 V
    - 15 Hz – 150 Hz: 10 to 1 V
    - 150 Hz – 1.5 kHz: 1 V
    - 1.5 kHz – 15 kHz: 1 to 10 V
    - 15 kHz – 150 kHz: 10 V
    EN 61000-4-17: 1999 + A2:2009
    Immunity to Ripple on DC input power port
    - DC 10% Un
    EN 61000-4-18: 2007 + A1:2010
    Immunity to damped oscillatory waves
    - Frequency 100 kHz / Repetition rate 40 s
    - Frequency 1 MHz / Repetition rate 400 s
    - Power port DC
      DC ± 1.25 kV line to line
      DC ± 2.5 kV line to ground
    - Data lines ± 2.5 kV line to ground
    EN 61000-4-29: 20001)
    Immunity to voltage dips and interruptions on DC input power port
    - 0 % Un on PWR1 – 0.05 s

  • SEC3-SA; IEC 61850-3; EN 61850-3: 2014

    The SEC3-SA hardware model meets the special requirements for electromagnetic compatibility and power supply described in Part 3 of the IEC 61850 standard.

    1) Only with the hardware model SEC3-SA.

Documentation
Manual
Datasheet
EU declaration of conformity
UKCA declaration of conformity